40kVA Modular UPS 3P:3P (40-520kVA)

40kVA Modular UPS 3P:3P (40-520kVA)

Flexibly Scalable Cabinets and Battery System

Modular UPS systems consist of independently running modules. UPS modules operate within different size cabinets each of which are built with 5-10-13 racks.

All modules of the UPS system can be monitored and controlled through an LCD panel located on the cabinet door.

Mechanical (Manual) Bypass switch and the circuit breakers are located in the cabinet.

Thanks to unique and special design of modular UPS, there is no need to access to the UPS from the sides and from the back; front access enables the addition of a module easily to increase capacity.

Why modular UPS

The most pronounced advantage of modular UPSs is the fact that they can exibit higher powers at a smaller space. Maximum available power must be supplied for critical applications such as data centers, where the available space for UPS installation is very limited and costly. Modular UPSs meet this requirement. Modular UPSs also consume less electrical energy due to their high operating efficiencies and hence pay off their initial investment in a short period of time.

Advantages of a modular structure:

  • Fast installation
  • Fast maintenance with no interruption in operation
  • Low maintenance cost
  • Low cost of capacity increase
  • N+X redundant mode of operation
  • Plug-and-play type power modules
  • Flexibly scalable UPS cabinet
  • Flexibly scalable battery cabinets

Modular systems for increasing capacity and high reliability

  • Highly reliable N+X architecture
  • kVA=kW, more active power owing to unity output power factor (It is possible to connect more loads to the output of same power rated UPS)
  • As your business grows, the capacity can be increased when needed due to its modularity (Possibility of expanding capacity by virtue of horizontal and vertical architecture)
  • High efficiency (low electric energy bills)
  • Fast and easy service due to modular structure (reduced service and maintenance costs)
  • No harmonic related problems on the utility mains due to its low input current THDi value (Increase in overall efficiency of the facility power distribution system)
  • Common battery for more than one UPS module
  • Wide range of input voltage and input frequency (Compatible with the electrical operating conditions worldwide)
  • Datacenter
  • Aiports
  • Factories
  • Emergency Power Systems
  • Smart Buildings
  • Security and Lighting Systems
  • Building Automation Systems and Special Telecommunication Applications
  • Hospitals
  • Construction Indusrty

This product is standard.

Input
Nominal voltage 380/400/415 VAC, (3Ph+N+PE)
Voltage range 208-478 VAC
Frequency range 40 – 70 Hz
Power factor ≥ 0.99
Bypass voltage range Max. voltage. 220V +25% (optional +10%, +15%,+20%) 230V 20% (optional +10%, +15%) 240V 15% (optional +10%) Min. voltage -45% (optional -20%, -30%) Frequency protection range. ±10%
Harmonic distortion (THDi) 2% (100% nonlinear load)
Generator input Support
Output
Output voltage 380/400/415 VAC, (3Ph+N+PE)
Voltage regulation ± 1%
Power factor 0.9/1 (Customized)
Output frequency 1. Line mode. ±1%, ±2%, ±4%, ±5%, ±10% / 2. Battery mode. (50/60 ±0.1%) Hz
Crest factor 3/1
Harmonic distortion (THDi) ≤ 2% with linear load / ≤ 5% with non linear load
Efficiency 95.5%
Battery
Battery voltage ± 240VDC; battery quantity (optional)
Charge Current UPS cabinet 130A (Max.)
Charge Current Module 10A (Max.) (charge current can be set according to battery capacity installed)
Backup time Depends on the capacity of external batteries
System Features
Transfer time Utility to battery
Overload Line mode Load ≤110%
Overload Battery mode Load ≤110%
Overload Bypass mode Breaker (10kVA
Short circuit Hold whole system
Noise suppresion Complies with EN62040-2
Communication interface UPS cabinet
Environmental
Operating temperature 0 ~ 40°C
Storage temperature -25 ~ 55°C
Humidity range 0 ~ 95% (non condensing)
Altitude < 1500m
Noise level< 65dB
Dimensions & Weight
Dimension D x W x H (mm) UPS cabinet 860 x 1200 x 2000
Dimension D x W x H (mm) Module 443 x 580 x 131 (3U)
Net weight (kg) UPS cabinet 860
Net weight (kg) Module 35
* Optional 10,15, 20 kVA available
** Diffrent Cabinets sizes available
Indicators & Alarm
LCD Panel UPS status, Load level, Battery level, Input/Output voltage, Discharge timer, Fault conditions
Alarm Battery mode, Low battery, Overload, Fault
Standarts & Certification
Security IEC/EN62040-1, IEC/EN60950-1
EMC IEC/EN62040-2, IEC61000-4-2, IEC61000-4-3, IEC61000-4-4, IEC61000-4-5, IEC61000-4-6, IEC61000-4-8