Real double conversion online technology

Online UPSs are an ideal choice especially for computers and other sensitive equipment. Online UPS completely isolates your equipment from the mains, charges its batteries from mains power and by using kinds of filters, supplies connected loads with power. As a result all unwanted conditions that may occur in mains are filtered by online UPS and your sensitive equipment is supplied with clean energy.

Real sine wave output

Fully compatible with all kinds of equipment. Ideal for medical and critical applications.

  • Real sine wave output

Fully compatible with all kinds of equipment. Ideal for medical and critical applications.

  • Wide input voltage range (110-300 VAC)

Online operation with very low and high voltages without using battery power.

  • Input power factor correction (PF=0.99)

Reduces consumed electrical energy and yields saving in electric bills.

  • High output power factor (PF=0.9)

15% more power at the output in comparison to standard 0.7 power factor UPS systems. Can support more equipment.

  • Smart charger technology for optimum battery performance

Provides longer battery life and lower operational costs due to special charging technique.

  • High performance microprocessor

Because of its CPU control, digital structure and high speed; UPS performs overload, short circuit, low-high voltage and overtemperature protections. By providing complete protection ensures a stable and reliable operation.

  • Multi Function Buttons

– 208/220/230/240 VAC Selectable Output Voltage
– 50/60 Hz Frequency Converter Mode
– EPO – Emergency Power Off

  • Datacenter
  • Aiports
  • Factories
  • Emergency Power Systems
  • Smart Buildings
  • Security and Lighting Systems
  • Building Automation Systems and Special Telecommunication Applications
  • Hospitals
  • Construction Indusrty

This product is standard.

Capacity
6kVA 10kVA
Input
Voltage range Low voltage transfer @50% load 110 VAC ± 3%, @100% load 176 VAC ± 3%
Voltage range Low voltage back transfer @50% load 120 VAC ± 3%, @100% load 186 VAC ± 3%
Voltage range High voltage transfer 300 VAC ± 3%
Voltage range High voltage back transfer 290 VAC ± 3%
Frequency range 46 Hz ~ 54 Hz or 56 Hz ~ 64 Hz
Power factor ≥0.99 (100% load)
Phase Single phase + Neutral + Ground
Output
Output voltage 208 / 220 / 230 / 240 VAC
Output power factor (PF) 0.9
AC voltage regulation (Batt. mode) ± 1%
Frequency range (Synchronized) 46 Hz ~ 54 Hz or 56 Hz ~ 64 Hz
Frequency range (Battery mode) 50 Hz ± 0.1 Hz or 60 Hz ± 0.1 Hz
Overload Line mode %100-110 > transfer to by-pass in 30min, %110-130 > transfer to by-pass in 5min, > %130 10sec
Overload Battery mode %100-110 > shuts down in 3min, %110-130 > shuts down in 30sn, > %130 10sec
Current crest ratio 3/1 max.
Harmonic distortion ≤%3 THD (linear load), ≤%5 THD (non-linear load)
Transfer time By-pass ↔ Inverter Line mode 0 msec
Transfer time Inverter ↔ By-pass Line mode 0 msec
Efficiency
Line mode ~ %92 ~ %93
Battery mode ~ %90 ~ %91
Battery
Standard model Type & number of battery 12V 9Ah x 16 12V 9Ah x 20
Standard model Charge time 9 hours for recharging up to 90% capacity
Standard model Charge current 1.0 A ± 10% max. 2.0 A ± 10%
Standard model Charge voltage 218.4 VDC ± 1% 273 VDC ± 1% (based on 20 pcs batteries)
Long run model Type & number of battery Type
Long run model Charge time Depends on external battery capacity
Long run model Charge current 4.0 A ± 10% max. 6.0 A ± 10%
Long run model Charge voltage 273 VDC ± 1% (based on 20 pcs batteries)
Indicators & Alarm
LCD Panel UPS status, Load level, Battery level, Input/Output voltage, Discharge timer, Fault conditions
Alarm Battery mode, Low battery, Overload, Fault
Dimensions & Weight
Standard Model D x W x H (mm) 369 x 190 x 688 442 x 190 x 688
Standard Model Net weight (kg) 72 82
Long run model D x W x H (mm) 369 x 190 x 318 442 x 190 x 318
Long run model Net weight (kg) 21 23
Environmental
Operating temperature 0-40°C
Humidity 0-95% RH (non-condensing)
Noise level (audible) < 55 dBA, from 1m < 58 dBA, from 1m
Management
Smart RS-232 or USB Windows 98/2000/2003/XP/Vista/2008, Windows¨ 7/8, Linux, MAC
SNMP (Optional) Power management from SNMP manager and web browser