Commercial UPS 3P:3P (40-120kVA)

Commercial UPS 3P:3P (40-120kVA)

Transformerless Structure

Use of transformerless technology results in a significant reduction in volume and weight of the UPS also improving the important ratio between power and foot print of the UPS. Because there is no transformer at the output of the inverter, the electrical losses of equipment decrease and efficiency increases. Increased efficiency lowers the cost of consumed electricity. In addition a transformerless UPS has lower accoustic noise. DC voltage level of traditional UPS is low, so in order to generate enough AC voltage at output, it needs a step up transformer in the inverter. The DC voltage level in transformerless UPS is already high enough, so there is no need for a step up transformer to be used.

  • High output power factor (PF=0.9)

15% more power at the output in comparison to standard 0.7 power factor UPS systems. Can support more equipment.

  • ECO Mode

Eco Mode enables the unit to supply the loads straight from the AC mains. In case of AC mains failure, the system will supply the load using battery power. In this way the efficiency is close to 100%. Eco Mode is used in less demanding applications.

  • Flexible Setup

The Hi-tech Pro II X9 series is a unit with high flexibility in adapting input and output, and may easily be set up depending on the requirements of the facility:

    • Three phase input / three phase output (3/3) only factory configurable
  • Parallel operation

Up to 3 units can be connected in parallel without additional hardware, to accommodate increased power demands as well as to attain power redundancy with high system integrity. All UPS ratings in the parallel system must be equal. Each UPS in the parallel system is controlled independently. Therefore the unit’s specific values, such as load sharing and mains synchronization are observed and controlled by each UPS control system making the necessary corrections.

  • Access

Considerations should be given for UPS design in several key areas, including electrical usages, communications, output compatibility, ratings, reliability etc., without any comprom, optimizing the UPS for easy maintenance. That is why important consideration has been given allowing generous access to the unit’s electronic cards and power components. At the same time, usage of sub-assembled units in the DC power bus and control section means less component count and results in less connection interfaces.

  • Data Centers
  • Aiports
  • Factories
  • Emergency Power Systems
  • Smart Buildings
  • Security and Lighting Systems
  • Building Automation Systems and Special Telecommunication Applications
  • Construction Indusrty
  • IT Networks
  • Financial Services
  • Telecommunication
  • Industrial Processes
  • nfrastructures (Hospitals / Airports / Tunnels)

This product is standard.

Capacity
40kVA 60kVA 80kVA 100kVA 120kVA
Input
Nominal voltage Single phase 220 V, 230 V or 240 V; Three phase 3 x 380 V, 3 x 400 V or 3 x 415 (4 wires)
Voltage range + 15% or – 20%
Frequency range 50 / 60 Hz ± 5%
Input current total harmonic distortion 100% load. THD-i < 1.0%50% load. THD-i < 2.0% 10% load. THD-i < 5.0%
Current limit High overload. PFC limit (discharging batteries)
Power factor 1.0
Output
Output voltage Single phase 220 V, 230 V or 240 V; Three phase 3 x 380 V, 3 x 400 V or 3 x 415 (4 wires
AC voltage regulation (Batt. modu) Stationary ± 1%, Transitory ± 2% (Load variations 100 – 0 – 100%)
Frequency range 50 / 60 Hz synchronized ± 4%, With mains absent ± 0.05%
Max. slow rate ± 10 Hz/s
Waveform Sinewave
Output voltage total harmonic distortion Linear load
Phase displacement 120 ± 1% (balanced load); 120 ± 2% (imbalance @ 50%)
Dynamic recovery time 10 msec @ 98% of the static value
Admissible overload 125% load 10 min, 150% load 1 min
Admissible crest factor 3.2/1.
Admissible power factor 0.9
Output voltage imbalance with 100% unbalanced load < 1%
Current limit Overload, Short circuit
Static By-Pass
Type Solid state
Voltage Single phase 220 V, 230 V or 240 V; Three phase 3 x 380 V, 3 x 400 V or 3 x 415 (4 wires
Frequency 50 / 60 Hz
Type of control Mikro processor based
Transfer time 0 sec
Admissible overload 400% load 10 sec
Transfer to By-pass Immediate, for overloads above 150%
Manual By-Pass (Maintenance)
Type Without interruption
Voltage Single phase 220 V, 230 V or 240 V; Three phase 3 x 380 V, 3 x 400 V or 3 x 415 (4 wires
Frequency 50 / 60 Hz
Efficiency
AC mode ~ 92.5%
Battery mode ~ 96.2%
Battery
Type VRLA Battery
Number of batteries 31 + 31
Charging time 8 hours for recharging up to 90% capacity
Charge current Set automatically according to battery capacity
Charging voltage – 420.0 VDC – 0 VDC + 420.0 VDC
Additional battery support Available
Additional charge current Set automatically according to battery capacity
Dimensions & Weight
D x W x H (mm) 770 x 450 x 1100
Weight (kg) 122
Indicators & Alarm
LCD Panel UPS status, Load level, Battery level, Input/Output voltage, Discharge timer, Fault conditions
Alarm Battery mode, Low battery, Overload, Fault, 100 record past events